Power System Blockset | ![]() ![]() |
Transient Performance for a Fault at Bus B2
The configuration of the substation circuit breakers normally allows to clear a bus fault without losing lines or transformers. You will now modify your case1
circuit in order to perform a three-cycle, three-phase-to-ground fault at bus B2 as shown on Figure 2-9:
Phase A, Phase B, Phase C, Ground Faults : all checked Transition times :[2/60 5/60] Transition status [1, 0, 1...]: (0/1)
You have now programmed a three-phase-to-ground fault applied at t=1 cycle.
Switching of Phase A: not checked Switching of Phase B: not checked Switching of Phase C: not checked
The circuit breakers will not be switched anymore. They will stay at their initial state (closed).
Copy the Multimeter block from the Measurement library into your case1
circuit. Open the Transformer dialog box. In the Measurements pop-up
menu, select Flux and magnetization Current. Open the Multimeter block.
Verify that you have six signals available. Select flux and magnetization
current on phase A, and click on OK.
Waveforms of interest are plotted on Figure 2-8.
Figure 2-8: Simulation Results for a 3-Cycle 3-Phase-to-Ground Fault at Bus B2
The 9 Hz subsynchronous mode excited at fault clearing is clearly seen on the phase A voltage at bus B2 (trace 1) and capacitor voltage (trace 3). The 9 Hz voltage component appearing at bus B2 drives the transformer into saturation
as shown on the transformer magnetizing current (trace 4). The flux in phase A of the transformer is plotted on trace 5. At fault application the voltage at transformer terminals drops to zero and the flux stays constant during the fault. At fault clearing, when the voltage recovers, the transformer is driven into saturation as a result of the flux offset created by the 60 Hz and 9Hz voltage components. The pulses of the transformer magnetizing current appear when the flux exceeds its saturation level. This current contains a 60 Hz reactive component modulated at 9 Hz.
Figure 2-9: S Series Compensated Network Used for a Fault at Bus B2
![]() | Frequency Analysis | Chopper-Fed DC Motor Drive | ![]() |